The weather turns rough for Thanksgiving in New York this year. As of Wednesday morning, the National Weather Service office in Upton has a High Wind Warning out for the five boroughs and Nassau and Suffolk counties from 10 AM Thursday to 1 AM Friday, with east winds of 25 to 35 mph and gusts up to 60 mph. The forecast also calls for steady rain Thursday into Thursday night, with 1 to 2 inches possible, and a Coastal Flood Warning for parts of Manhattan, southern Queens and the south shore. The NWS warns that widespread power outages are expected.
Temperatures, on the other hand, stay mild. The Manhattan forecast has highs in the 50s and lows in the 40s through early next week, with no freezing nights in sight. So this storm isn't about cold. Wind, water and lost power are what put HVAC equipment at risk this week.

Before the wind picks up
- Secure anything loose on the roof. Panels, access doors, filter rack covers, line set covers and condensate piping all need to be fastened. Remove stored material, empty boxes and leftover strut from around the equipment. Gusts near 60 mph can turn them into debris.
- Clear roof drains and scuppers near equipment. With an inch or two of rain, water has to get off the roof. If it ponds around curbs and dunnage, it can find its way into the building.
- Check intakes and louvers. Wind-driven rain can be pulled into outdoor air intakes on ERVs, rooftop units and makeup air units. Make sure hoods, screens and louvers are intact and dampers close the way they should.
- Look at the cellar too. In flood-prone areas near the coast, check sump pumps and get stored materials off the floor of mechanical rooms.
If the power goes out
VRF/VRV heat pump systems, rooftop units and their controls all depend on power. When the power comes back, don't keep resetting equipment that won't start. Some outdoor units need power restored for a while before the compressor is allowed to run, so follow the manufacturer's instructions. Write down any error codes on the outdoor units, indoor units and central controllers. A qualified technician can sort out a protective lockout from a real fault. Check that schedules and setpoints on the building controls didn't reset to defaults.

After the storm
The forecast turns mostly sunny for Saturday, which makes it a sensible day for a roof walk once the wind has died down. Things to look for:
- Outdoor units, curbs or stands that shifted, and coil fins bent by flying debris
- Torn or missing insulation and covers on refrigerant line sets
- Water inside electrical disconnects or control panels
- Leaks at rooftop duct seams and curb flashing, which often show up as ceiling stains on the top floor
- Cooling towers: debris in the basin if the tower is still running, or loose covers if it has already been shut down for the season
Because the forecast stays above freezing into next week, heating loads should be light, which leaves a window to fix storm damage before the cold arrives.
Request a quote
If the storm damages rooftop VRF/VRV equipment, ductwork or piping, or you're planning replacements for next year, send photos, drawings or project details through Request a Quote or call (718) 616-8611. Superior HVAC is a Mitsubishi Electric Diamond Commercial Contractor working across Manhattan, Brooklyn, Queens, the Bronx, Staten Island and Long Island. For more on seasonal prep, see Getting Commercial HVAC Ready for a New York Winter and A Mild Week in November: Rooftop HVAC Checks to Do Before the Cold.
Get in touch
Request a quote
Send drawings or tell us about your project. Bid invitations welcome.
(718) 616-8611Email[email protected]
Office226-10 Jamaica Ave, 2nd Floor, Floral Park, NY 11001